Block valve RQJ - * / * g (s)

Block valve RQJ - * / * g (s)

When any abnormality in the system causes the monitoring pressure to reach the predetermined warning value (ultra-high pressure or ultra-low pressure), the device will cut off the air flow automatically and quickly, which plays a role of safety protection.

Product characteristics

High cutting accuracy and fast response

  • internal bypass, easy to open

  • it can be used for ultra-high pressure and ultra-low pressure cut-off and closed tightly.

  • it can be cut off automatically or manually by using the medium's own pressure

  • remote control, monitoring and alarm can be selected

  • easy operation and online maintenance
    Compact structure and convenient installation

  • when the medium contains corrosive substances such as sulfur and benzene, anti-corrosive materials can be selected

  • applicable media: natural gas, artificial gas, liquefied petroleum gas, air and other non corrosive gases

  • it can be used for gas transmission pipeline, city gate station, regional pressure regulating station, industrial gas and civil gas between the mine gas gathering station and city gate station.

Main technical parameters

  • cut off pressure PQ: 2KPa ~ 10KPA; 7kpa ~ 24kpa; 30KPa ~ 300kPa
    0.03Mpa-0.5Mpa; 0.4Mpa-0.8Mpa; 0.7Mpa-1.3Mpa;1.2Mpa-1.7Mpa; 1.6Mpa-2.6Mpa; 2.5Mpa-4.0Mpa;4.0Mpa ~ 7.6Mpa

  • cutting accuracy: ± 3%

  • working temperature T: - 20 ℃ ~ 60 ℃

  • nominal pressure: pn0.4 pn0.8 pn1.6 pn2.5 pn4.0 pn6.4 pn10.0

  • nominal diameter: DN25 DN50 DN80 DN100 DN150 DN200

Main structure and installation dimension

ModelLHH1

Less than PN16PN25、PN40More than PN63

RQJ-25/*G(S)184197210382301
RQJ-50/*G(S)254267286460328
RQJ-80/*G(S)298318337520346
RQJ-100/*G(S)352368394522357
RQJ-150/*G(S)451473473625407
RQJ-200/*G(S)543568568787519